n addition to smoke detection a optical smoke sensor, the detector is provided with a built-in alarm
signaling device. It is provided with an integrated isolator.Alarm signaling
The alarm signaling device is activated by the control panel. No further short address needs to be allocated.
It is programmed with tools 8000 as of software version 1.05. Alarm tone / speech message programming
(depending on type)
For detectors with speech message and / or alarm tone function with up to five language options, up to 4
signals can be programmed. Two signals are reserved for alarm signaling and evacuation in the case of
fire. Two further signals can be programmed for other events. Each signal can consist of up to four signal
components, enabling one signal to be programmed as a DIN tone combined with subsequent speech
messages in three different languages. Alarm tones can be chosen from a table with various tone types.
For application in schools, a break signal to signify the breaks between class can be activated.
When the basic setting is selected, signals / signal components can be continuously repeated until the
signaling function is interrupted by the control panel. They can also be programmed with a repetition rate of
one to three times. Thus, the break signal in schools can be deliberately set to only one repetition. In the
same way, the total signal can be set to continuous repetition, with the DIN tone being played only once
while subsequent speech messages are played up to three times. Sound pressure programming
The sound level [dB(A)] can be set to eight levels, from approximately 64dB (A) to approximately 92dB (A).

Accessories:
767800 Mounting bracket
805590 Standard detector base for IQ8Quad