The IDP-CONTROL is an addressable notification module for use with
Honeywell Farenhyt Series fire alarm control panels (FACPs). The IDP-CONTROL gives you the flexibility to add notification circuits wherever
they are needed on an Farenhyt FACP signaling line circuit (SLC) loop.
The IDP-CONTROL provides supervised monitoring of wiring to load
devices that require an external power supply to operate, such as bells,
horns, and strobes. It is capable of Class B and Class A supervision.
Upon command from the FACP, the IDP-CONTROL will disconnect the
supervision and connect the external power supply across the load device.
The disconnection of the supervision provides a positive indication to the
panel that the control relay actually turned on. The external power supply
is always relay isolated from the SLC loop, so that a trouble condition
on the power supply will never interfere with the rest of the system.
INSTALLATION
The IDP-CONTROL mounts directly into a 4” square electrical box. The
box must have a minimum depth of 2-1/8”. A surface mount electrical
box (System Sensor® PN SMB500) is available from Honeywell.
COMPATIBILITY
The IDP-CONTROL is compatible with the following Farenhyt Series FACPs:
• IFP-2100 / IFP-2100ECS / RFP-2100
• IFP-2000 / IFP-2000ECS / RPS-2000
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
IDP-CONTROL Technical Specifications
PHYSICAL
Dimensions: 4.5″ H x 4″W x 1.25″ D
Shipping Weight: 6.3oz (196g)
ELECTRICAL RATINGS
Operating Voltage: 15 to 32VDC
Standby & Alarm Current: 350 μA
End-of-Line Resistance: 47kW
SLC Loop Impedance: 40W
ENVIRONMENTAL
Operating Temperature: 32º-120ºF (0ºC – 49ºC)
Humidity: 10 to 93% non-condensing)
ORDERING INFORMATION
IDP-CONTROL: Notification module
ACCESSORIES
SMB500: 4” Square Surface Mount Electrical Box
CB500: Module Barrier. Used to separate power
limited and non-power limited wiring in a junction
box.