Overview
An extensive range of interfaces are available
to support the Cooper range of UL intelligent
addressable control panels, providing
solutions for most design requirements.
The UL zone monitor unit (ULMIU872) is an
extremely compact unit ideal for incorporation in
external equipment, it is a single zone input unit,
soft addressed and incorporates integral short
circuit isolators.
It is suitable for interfacing a zone of up to 20
Cooper UL conventional detectors onto a
Cooper UL intelligent addressable control panel.
It will operate with any Cooper UL conventional
detector in configuration with the UL
conventional base (CB2E).
Benefits
• Quick and simple to install
• No hard addressing required
(Plug and play)
• Compact size
• Easy to expand a system
using existing wiring
Dimensions

Mounting Details (Back-Box)

Installation
1. Fit the unit in position in accordance to the
mounting details.
2. Connect the unit according to standard
connections.
3. Up to 3 units can be fitted inside a micro
module box unit.
Operation
Normal Standby / Alarm / Alarm Test /Alarm
Silence / Alarm Reset / Trouble /Trouble Silence
/ Off normal position of switches
Technical Specification

Standard Connections

Note:
1. This unit can only be used with Cooper UL conventional detector base and compatible
detectors.
2. Only connect cable screen to its adjacent earth terminal.
3. The end of line resistor must always be fitted, even if the spur is unused. Installer /
service engineer must ensure it is fitted.
4. Maximum number of conventional pull stations allowed is unlimited.
5. Detector zone end of line device is 5k6 (supplied).
6. Compatibility Identifier ULCV1.
7. Recommended cable type FPLP (plenum cable), type FPLR (riser cable), or type FPL.

Product Codes