Features:
• Max. two micromodules (system supports up to 254 digital loop addresses in total)
• Max. two esserbus analog loop modules
• Short circuit and open circuit resistant loop operation
• Loop installation with I-Y(ST)Y 0.8 mm cable for a maximum length of 3.5 km
• Up to 127 esserbus devices (fire detectors and/or manual call points)/detector zones per loop
• Up to 32 esserbus transponders per loop/operation
of wireless components (see chapter 10)
• Operation types TM and PM as per DIN VDE 0833
– 2 to avoid unwanted alarms being triggered
• Fire brigade operating panel and alarm transmission unit interface on the peripheral module
• Three common relays, freely programmable, monitored, floating for up to 24 V DC/1A (on the
peripheral module)
• TTY or RS 485, RS 232 interface
• Integration in the short circuit and open circuit resistant essernet network with up to 31 fire
detection panels depends on transmission rate
• Connection to graphical supervisor FlexES Guard/WINMAG via serial essernet interface (SEI)
• Operating panel with alphanumerical display
• Large display with 8 rows with 40 characters. As follows rated – four rows with 40 characters for the
status information (first and last message), and the other four rows with 40 characters are used for
system information e.g. “Sounders Off”
• Event memory for up to 10,000 events
• All System 8000 micromodules are compatible
• Printer interface for internal printer
• Two batteries with monitoring circuit
• Monitored input for external power supply unit
• Degraded mode for monitored areas up to 48,000 m² or more than 512 fire detectors acc. to the
German Planning standard VDE 0833 and/or VdS 2095
• Max. 2 analog powered loop modules (System supports up to 254 digital loop addresses in total)
• BUS powered, synchronously controlled, acoustic
alarm signaling devices as per DIN EN 54-3 with alarm tone as per DIN 33404
• Up to 48 powered loop base sounders (Series 9200) per loop
• Up to 32 powered loop IQ8Alarm / IQ8Alarm Plus devices per loop
• Up to 64 powered loop IQ8Alarm Plus So / FSo devices per loop
• Up to 48 IQ8Quad with alarm device per loop