Description
The FH-340 Horn allows for a number of applications
on a single device. The horn settings include Temporal,
Non-Temporal, March Time and a Chime sound. The
horn also has Low, Mid and High volume settings for
each pattern and tone. The tones include 2400 Hz,
Electro-Mechanical, Broadband and Chime.
The voltage input can be either regulated DC or full
wave rectified (FWR) 12 volt or 24 volt operation.
The FH-340 utilizes a universal mounting plate that
will mount on a single gang, double gang, octagon and
4” square electrical boxes. Outdoor installations must
use either the BB-206WP 4-inch square weatherproof
bell backbox or the BBX-5 weatherproof backbox.
The back plate allows the installer to mount the plate
and terminate the wire connections. The horn attaches
in a hinge fashion from the top and is secured by a
single mounting screw. The horn completely covers
the mounting back plate, therefore it can be mounted
before other trades work is completed and not affect
the final look.
Engineering Specifications
The installer shall provide and install the FH-340
indoor/outdoor selectable horn. The horn shall have
thirty-three (33) different settings. The horn shall be
selectable for continuous (non-temporal), temporal
(ANSI Code 3) and March Time patterns. The
horns shall have a 2400 hertz, Electro-Mechanical,
Broadband or a Chime tone.
Each of the patterns and tones shall be selectable
for a Low, Mid or High volume setting. The horn
shall operate at 12 or 24 VDC regulated or full wave
rectified. The horn shall have an operating range
between 8 and 33 VDC. The horn shall utilize a
mounting plate that allows the installer to pre-wire the
mounting plate. The mounting plate shall be universal
and mount on a single gang, double gang, octagon
or 4 inch square box. If the horn is needed in a wet or
outdoor installation, it shall be mounted on either a BB206WP 4-inch square back box or a BBX-5 outdoor
matching back box. The horn shall have a gasket on
the back plate that seals the electrical connection of
the terminal connection. The mounting plate shall be
completely covered by the horn and shall be secured
by a single screw. Operating temperature range will
be 32°F to 120°F (0°C to 49°C) for indoor model and
-40°F to 151°F (-40°C to 66°C) for outdoor model.
The horn shall be UL listed to standard 464, Audible
Signaling Devices. In addition, the device shall be
C-UL listed to CAN-ULC S525.

Specifications


Installation

Wiring Diagram

Dimensions 6 5/64 (154.4)

Dipswitch Settings


Specifications

Ordering Information