The IDP-Heat, IDP-Heat-HT, and IDP-Heat-ROR are plug in thermal
detectors, with integral communication, that provide features that
surpass conventional detectors. These thermal detectors are for use
with Honeywell Farenhyt series fi re alarm control panels (FACPs).
Detector sensitivity can be programmed from the FACP software.
Sensitivity is continuously monitored and reported to the FACP. Point ID
capability allows each detector’s address to be set with rotary address
switches, providing exact detector locations for selective maintenance
when chamber contamination reaches unacceptable levels.
IDP-Heat is a fi xed temperature thermal detector that uses a thermistor
sensing circuit to produce 135ºF (57ºC) fi xed thermal detection.
IDP-Heat-HT is a variable high temperature detector that provides
high temperature detection at 135ºF – 190ºF (57ºC – 88ºC).
IDP-Heat-ROR is a fi xed temperature and rate-of-rise
thermal detector that uses a thermistor sensing circuit
to produce 135ºF (57ºC) thermal protection..
Compatibility
The IDP-Heat, IDP-Heat-HT, and
IDP-Heat-ROR are compatible with
the following IDP series bases:
• B210LP 6” Mounting Base
• B501 4” Mounting Base
• B224BI 6” Isolator Base
• B224RB 6” Relay Base
• B200SR 6” Sounder Base
The IDP-Heat, IDP-Heat-HT, and IDP
Heat-ROR are compatible with the
following Farenhyt Series FACPs:
• IFP-2100 / IFP-2100ECS / RFP-2100
• IFP-2000 / IFP-2000ECS / RPS-2000
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
IDP-Heat, IDP-Heat-HT and IDP-Heat-ROR Technical Specifications

IDP-CONTROL Technical Specifications
SPECIFICATIONS*
Physical:
Height: 2.0” (5.08cm)
Diameter: 4.1″ (10.4CM) installed in B501 base.
6.1″ installed in B210LP base
Shipping Weight: 4.8oz
ELECTRICAL RATINGS
Operating Voltage: 15 – 32VDC
SLC Standby and Alarm Current: 300 μA
ENVIRONMENTAL
Operating Temperature
IDP-Heat & IDP-Heat-ROR: -4°F – 100 °F (-20°C
– 38°C)
IDP-Heat-HT: -4°F – 150 °F (-20°C – 66°C)
Humidity: 10 to 93% non-condensing)
THERMAL RATINGS
IDP-Heat: Fixed temperature setpoint 135ºF
(57ºC)
IDP-Heat-HT: High temperature heat 135ºF –
190ºF (57ºC – 88ºC)
IDP-Heat-ROR: Rate-of-rise detection 15ºF/min
(9ºC/min)
ORDERING INFORMATION
IDP-Heat: Fixed temperature thermal detector
IDP-Heat-HT: Fixed high temperature thermal
detector
IDP-Heat-ROR: Fixed temperature and rate-of-rise thermal detector
ACCESSORIES
RA100Z: Remote LED Annunciator.
XR2B: Detector Removal Tool. A removal and
replacement tool for IDP plug-in detectors.
Includes the T55-127-000.
M02-04-01: Detector test magnet
M02-09-00: Test Magnet with telescoping handle
XP-4: Extension pole for XR2B. Extends from 5 –
15 ft.
T55-127-000: Detector removal head.
BCK-200B: Black detector kit. For IDP-series
detectors.
* Unless otherwise noted, specifications apply to