The IDP-PULL-SA is a single action pull station requiring only one motion
to activate the station. The IDP-PULL-DA is a dual action pull station
requiring two motions to active the station. Both pull stations are designed
to work with Honeywell Farenhyt series fire alarm control panels (FACPs).
INSTALLATION
The IDP-PULL-SA and IDP-PULL-DA can be surface mounted to an SB-I/O
surface back box or semi-flush mounted on a standard single-gang with a
minimum depth of 2.13”(5.40 cm) or double gang or 4” (10.61 cm) square
electrical box. You can also use the optional (System Sensor® PN BG-TR)
trim ring if the station is being semi-flush mounted.
COMPATIBILITY
The IDP-PULL-SA and IDP-PULL-DA are compatible with the following
Honeywell Farenhyt Series FACPs:
• IFP-2100 / IFP-2100ECS / RFP-2100
• IFP-2000 / IFP-2000ECS / RPS-2000
• IFP-1000 / IFP-1000ECS
• IFP-300 / IFP-300ECS
• IFP-100 / IFP-100ECS
• IFP-75
• IFP-50
IDP-PULL-SA and IDP-PULL-DA Technical Specifications

IDP-CONTROL Technical Specifications
SPECIFICATIONS*
Physical: 5.5″ H x 4″ D ( 14cm x 10.2cm)
Shipping Weight: 5.4oz
Housing Material: LEXAN polycarbonate resin
Bi-Colored LED:
Blinking Green: Normal
Steady Red: Alarm
Switch: Single pole, single throw (SPST) normally
open (N/O) switch which closes upon activation of
the pull station
ELECTRICAL RATINGS
Operating Voltage: 15 – 32VDC
SLC Standby and Alarm Current: 350μA
Wire Gauge: Up to 12AWG (3.1 mm2)
ENVIRONMENTAL
Operating Temperature: 32º-120ºF (0ºC – 49ºC)
Humidity: 10 to 93% non-condensing)
ORDERING INFORMATION
IDP-Pull-SA: Single Action Pull Station
IDP-Pull-DA: Dual Action Pull Station
ACCESSORIES
BG-TR: Optional trim ring.
SB-I/O: Surface backbox, indoor/outdoor.
* Unless otherwise noted, specifications apply to
IDP-Pull-SA and IDP-Pull-DA