The UL pull stations, UMPS-100 and UMPS-200, are
designed to exceed your expectations and offer the most
polished, feature rich and cost effective solution.
Both the UMPS-100 and UMPS-200 are compatible
with the Eaton UL range of intelligent addressable fire
systems, and come complete with a ULMCIM-C fast
response intelligent addressable input initiating unit.
This UL pull station is constructed of high quality, diecast metal for long lasting performance and is designed
to be fitted to a single gang back-box for flush mounting.
For surface mounting a sheet metal back box (SGB32S)
can be utilised.
The UMPS-100 and UMPS-200 are painted red with
raised white lettering, have a locking mechanism to
prevent unauthorized reset and are complete with a
UL listed fast response intelligent addressable input
initiating module (ULMCIM-C).
Technical specification

Surface mount
A surface mount installation uses a die-cast (model SGB-32C) or
sheet metal (model SGB32S) back box. The back box has 4 predrilled
mounting holes of 0.187” diameter. A size 8 screw can be used to
attach the back box to the wall surface. After the back box is in place,
attach the conduit. The cast back box has an opening that is tapped
for a ½ NPT fitting which may be oriented at the top or bottom when
the box is attached to the wall. The sheet metal back box has top and
bottom conduit knockouts. Field wiring is connected as shown in the
supplied wiring diagram. Please note that field wiring should not be
wrapped around the terminal screws but connected to the clamping
connections on the ULMCIM-C interface.
The front housing of the pull station is locked using either a key or a
hex lock depending on the model purchased. Unlock the front housing
and swing it forward to expose the metal mounting plate. Install the
mounting plate to the back box using the ¼” screws (4) supplied. If a
break rod is being used, move the pull handle to a 45 degree angle and
insert the break rod into the cavity beneath the pull handle. Place the
pull handle back in the normal standby position (flush with the surface
of the front housing).
Verify that the switch actuator is in the proper standby position before
moving the front housing back to the upright position and locking it.
Flush mount
Most flush mount installations may be attached to a standard single
gang box (not supplied).
Open the station as described above and mount it to the box using the
two holes located along the centre line of the mounting plate.
Conventional single action pull station
The cost effective conventional versions of the pull station must
be used in conjunction with ULMIU872 micro zone monitor unit or
ULCZMU352 zone monitor unit.
Dimensions

Intelligent addressable connection

Operation
The UMPS-100/UMPS-200 are operated by pulling the white handle on
the front of the pull station as far down as it will go, at which point the
handle locks into place and is easily visible from up to 50 feet.
The handle is reset by opening the pull station with a key, placing the
white handle in the normal upright position and relocking the station
Catalogue numbers